Specifications 1.fire alarm 4 zones conventional alarm controller

2. Suit for factory, building, business, etc

3. Fire alarm system

high stability industrial digital fire alarm control panel
  Features
1. 4 zone, 8 zone,16 zone optional 
2. All zones accept conventional detectors and any normally open
3. Max 25pcs conventional detectors in one zone
4. Support auto/manual for test
5. Each Zone can be disabled
6. Support backup battery   Technical specification  

AC Power

Power

110-270V AC 50 /60 Hz

Wire size

minimum #14 AWG (2.0 mm2) with 600V insulation

Battery (lead acid only)

Maximum Charging Circuit

Normal Flat Charge27.6V @ 0.8 amp

Maximum Charger Capacity

18 Amp Hour batter

Sound Output Device Circuits

General Alarm Zones 1 through 16

Operation: All zones Class B

Normal Operating Voltage

Nominal 24 VDC (ripple = 100 mV maximum)

Alarm Current

15 mA threshold

Short Circuit Current

42 mA maximum

Maximum Loop Resistance

100 ohms

End-of-Line Resistor

4.7K, ½ watt

Detector Loop Current is sufficient to ensure operation of two alarmed detectors per zone

Standby Current

7.26 mA

Three Relays Output

Relay contact rating

2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30 VAC (resistive)

Nonresettable 24 VDC Power

Maximum ripple voltage

10 mVRMS

Operating Voltage nominal 24 volts

Total DC current available from this output is up to 500 mA

Recommended maximum Standby current is 150 mA