Reactive Voltage Of 3 Phase Power Meter Calibrator For Standard Deviation Measurement
Product Profile:
AT6023C can calibrate and test multiple types of active & reactive energy meters, also can be used as a harmonic power output source.
Main Features:
- Automatically or single-step manually test basic error, creep, start, standard deviation of single/three
- phase energy meter, besides, automatically testing can be self-defined by user;
- Automatic Calibration System can be customized according to customer's requirements;
- Exchange the testing settings and testing records thru U disk(or SD card);
- Accuracy :U, I, P, kwh : ±0.05%; Q, kvarh : ±0.1%;
- U, I, P stability : 0.01%RG/3min, AC Voltage and AC Current distortion : ≤0.2%;
- Measurement scope: Voltage 57.7V- 660V; Current 1A-50A;
- Output 2nd-63rd harmonics, and measure & analyze the harmonics;
- 7" color touch screen, interface friendly, easy to operate;
- Equipped with RS232 & Ethernet interface, AT6023C can be operated either stand-alone, or controlled by PC;
- Remotely updating online, easily achieve software updating;
- Equipped with barcode gun interface, parameters of tested meters can be easily scanned in;
- Communicate with tested meters thru RS485, Ethernet, RS232;
- Self-protection, alarming and displaying overload location for Equipment output overload, Voltage
- short-circuit, Current open-circuit;
- Self-diagnosis for Amplifier failure and Internal module communication failure;
- Test energy meters with the accuracy of Class 0.2 and below (Class 0.05 equipment);
Technical Specification
|
Range |
Capacity |
Adjustment Degree |
Adjustment Range |
Stability |
Distortion (linear load) |
Measurement Accuracy |
AC Voltage |
57.7V~660V |
20VAmax/ phase |
0.01%RG |
0~120%RG
|
0.01%RG 3min CL0.05 0.02%RG 3min CL0.1 |
0.2% CL0.05 0.5% CL0.1 |
±0.05%RG CL0.05 ±0.1%RG CL0.1 |
AC Current |
1A~50A |
50VAmax/ phase @50A |
0.01%RG |
0~120%RG
|
0.01%RG 3min CL0.05 0.02%RG 3min CL0.1 |
0.2% CL0.05 0.5% CL0.1 |
±0.05%RG CL0.05 ±0.1%RG CL0.1 |
Phase |
0.00°~359.99° |
|
0.01° |
0.00°-359.99° |
0.01° |
|
±0.05° |
Frequency |
40Hz ~70Hz |
|
0.002Hz |
40Hz -70Hz |
0.002Hz |
|
±0.003Hz |
Power/Energy |
|
|
|
|
|
|
±0.05%RG CL0.05 ±0.1%RG CL0.1 pf≥0.5 |
Output Harmonics |
2nd to 63rd |
|
0.01%RG |
≤40% |
|
|
|
Other Parameters
Aux. Power supply |
AC 220V±15% |
Working Environment |
Environment Temperature 20℃-30℃, Humidity:RH ≤85% |
Dimensions |
500mm(L)×440mm(W)×155 mm(H) |
Weight |
22KG |
LCD Size |
7 inch color touch screen |
Competitive advantage :
We can follow the Customer-oriented principle, Artel Tech. aims to innovate hi-tech products and provide comprehensive solutions continuously, and continue to offer qualified products and excellent services to its global customers.
Artel's successful strategy is reflected in the number of certifications, including ISO9001 and CE quality system certification, Software Enterprise certificate issued by National Information Department, and hi-tech company certificate issued by government, etc.